The AHU air handling unit mainly relies on the rotation of the fan to drive indoor (outdoor) air to exchange heat with the internal coils of the unit, and filter impurities in the air to maintain indoor temperature, humidity, and air cleanliness by controlling the outlet air temperature and air volume. The AHU air handling unit can not only handle indoor air index processing (return air condition), but also introduce fresh air from the outside for processing (fresh air condition).
- Composition of AHU air conditioner
The functional components of AHU air conditioners generally need to be freely combined according to the specific situation of the user, and the order of combination varies among different manufacturers. However, generally speaking, AHU air conditioners mainly consist of the following functional segments:
- Fresh air section
The fresh air section mainly receives outdoor fresh air and settles impurities in the fresh air; Install the air valve actuator (opening and closing amount) for the fresh air valve, which is interlocked with the fan. It is recommended to install a temperature sensor in the shaded outdoor area for compensating the return air temperature.
- Filter section
The general method for filtering fresh air is primary (or coarse) filtration, which mainly filters out impurities with larger volumes; The filter after the return air section is generally a medium efficiency filter, which filters out impurities with smaller volumes; If it is a purification air conditioner, there will also be sub high efficiency and high-efficiency filtration sections. All filter screens should be equipped with differential pressure switches before and after to detect the cleanliness of the filter screen. If there are too many impurities blocking, an alarm signal will be issued.
- Return air section
The return air section is mainly suitable for mixing fresh air and return air; The air valve at the return air outlet is equipped with an air valve actuator (analog quantity) to regulate the return air volume. When the outdoor temperature is hot or cold in the season, the return air is utilized to the maximum extent possible while ensuring a certain amount of fresh air, thus achieving energy conservation. The exhaust valve at the exhaust outlet is equipped with an air valve actuator, which is interlocked with the return air valve actuator and operates in the opposite direction. A temperature and humidity sensor is installed on the return air pipeline to detect the greenhouse temperature of the return air (thus knowing the average indoor temperature and humidity), providing a basis for controlling the cold water valve, heating valve, electric heating and humidification valve.
- Cold section
The surface cooling section is mainly used to cool the air sent indoors and also has the function of cooling and dehumidifying (optional), with priority given to dehumidification. A temperature regulating valve (three-way) is installed at the inlet of the surface cooler. When the return air temperature and humidity reach the set requirements, the temperature regulating valve is turned down or closed, and excess chilled water flows back through the third passage to prevent the pressure difference before and after the regulating valve from being too large when it is turned down or closed, which may cause damage to other pipes or water pumps and affect the service life of the regulating valve. In addition, an anti freezing switch is installed on the surface of the surface cooler to protect the air conditioning equipment and is interlocked with the fan and air valve.
- Heating section
The heating section is used in winter (or dehumidifies and generates temperature after supercooling), and its working principle is the same as that of the surface cooling section. The surface coolers for heating and cooling of the two control systems are shared.
- Electric heating
Electric heating is generally used when the heating section cannot meet the heat requirements or when dehumidification causes overheating.
- Humidification section
The purpose of the humidification section is to prevent dry humidification in winter or special process requirements for humidification. The humidification method is generally wet film humidification or steam humidification.
- Air supply section
The function of the air supply section is to supply air indoors, also known as the fan section. The air valve at the air supply outlet is generally equipped with an actuator (switch quantity, optional function), which is interlocked with the fan.