Explosion-proof workshops, as special locations involving the production and processing of Class A and B flammable and explosive substances, are directly related to personnel safety, equipment and property protection, and production continuity. Their design must strictly adhere to building fire protection codes and standards, combining material characteristics and process flows to construct a comprehensive explosion-proof protection system. Specific requirements are as follows:
The floor is the foundation of explosion-proof protection, with the core objective of preventing frictional sparks and the accumulation of flammable materials. For production workshops emitting flammable gases heavier than air, flammable liquid vapors, and Class B production workshops with dust or fiber explosion hazards, non-sparking flooring materials must be used. During construction, the floor must be flat, without cracks or depressions to prevent flammable materials from accumulating in gaps. Simultaneously, a drainage slope of 1% to 3% should be provided, along with explosion-proof floor drains and sewage ditches, to ensure rapid drainage of leaked flammable liquids and reduce the risk of vapor accumulation. Interior wall design must balance cleanliness and explosion-proof properties. For workshops where combustible dust may accumulate, the wall base layer should be thoroughly plastered and compacted to eliminate pores and cracks, then coated with a washable, anti-corrosion paint to form a smooth, dense protective layer. This prevents wall material from peeling off and generating dust, while also facilitating daily cleaning.
Personnel safety is the core principle of explosion-proof design. Offices, rest rooms, and other densely populated auxiliary rooms are strictly prohibited in Class A and B explosion-hazardous production workshops to prevent mass casualties in the event of an explosion. If auxiliary facilities are necessary for production, they should be located in a separate area outside the workshop, maintaining a safe distance of at least 15 meters from the production workshop. The two areas must be completely separated by non-combustible walls with a fire resistance rating of at least 3.15 hours, and no doors or windows should be provided in the walls. If connecting passages are necessary, Class A fire doors with automatic closing devices must be installed, along with independent evacuation staircases to ensure rapid evacuation of personnel from the auxiliary area in an emergency.
Electrical equipment is the primary ignition source in explosion-proof workshops, and its selection, installation, and maintenance must strictly adhere to explosion-proof standards. All electrical equipment within the workshop must be selected according to the explosion hazard level, type of flammable material, and environmental conditions of the area; non-explosion-proof equipment is strictly prohibited. For example, intrinsically safe and explosion-proof equipment should be used in Zones 0 and 1 where flammable gases are continuously present; dust explosion-proof equipment must be used in dust explosion hazard areas. During installation, ensure that the equipment casing is intact and undamaged, and that the seals on key components such as junction boxes and cable entry devices are complete and effective; cables should be protected by conduits or laid in cable trenches, and the metal casing and supports of the equipment must be reliably grounded to prevent static electricity buildup and discharge; the operating temperature of electrical equipment must not exceed the ignition temperature of flammable materials, and forced cooling devices should be provided when necessary.
Electric sparks caused by lightning are a significant safety hazard in explosion-proof workshops, necessitating the construction of a comprehensive lightning protection system. Lightning protection devices should be installed on the workshop buildings. Install lightning protection strips. For workshops with a high explosion hazard level, in addition to the building's own lightning protection devices, independent lightning rods should be installed around the perimeter to ensure that the protection range covers the entire workshop and surrounding critical areas. Static electricity accumulation can also cause explosions; all metal equipment, pipes, and containers within the workshop must be equipotentially bonded and reliably grounded. Operators must wear anti-static work clothes and anti-static shoes; wearing synthetic fiber clothing is strictly prohibited to prevent the danger caused by static electricity from the human body.
Furthermore, explosion-proof workshops must be equipped with complete ventilation systems, fire-fighting facilities, and evacuation routes to form a comprehensive safety protection system and build a solid barrier for production safety.