Fan Filter Unit (FFU) ——essential Part Of The Cleanroom

Selecting the appropriate fan filter unit (FFU) requires a comprehensive consideration of multiple factors such as the cleanroom grade, application scenarios, performance parameters, installation and maintenance.

1. Clearly define the grade and requirements of the cleanroom

1.1 Cleanliness Grade

According to specifications such as ISO 14644 or Federal standard 209E, determine the target cleanliness level (for example, ISO level 5 corresponds to level 10,000, and ISO level 4 corresponds to level 1,000). The filtration efficiency of FFU should meet the grade requirements:

ISO grade 5 and below (medium and low range) : A combination of primary efficiency and high efficiency (HEPA, filtration efficiency ≥99.97%@0.3μm) can be selected.

ISO grade 4 and above (high grade) : Ultra-high efficiency filters (ULPA, filtration efficiency ≥99.9995%@0.12μm) are required.

Example: The semiconductor lithography workshop requires ISO level 3 (level 100) and FFUs equipped with ULPA filters.

1.2 Application Scenarios

Laboratory/Medical: Attention should be paid to stable air volume, noise control (≤65dB), and antibacterial design.

In electronic manufacturing, FFUs with low vibration (vibration velocity ≤0.5mm/s) and low energy consumption should be given priority to avoid interference with precision equipment.

Biomedical (including live bacteria operation) : Explosion-proof FFU must be equipped, and the filter must support in-situ sterilization (such as high-temperature steam or chemical fumigation).

2. Structural and installation compatibility

2.1 Dimensions and Installation Methods

Standard size: The common specification is 1175×575×320mm (applicable to 600×600mm ceiling frames). The height of the ceiling space needs to be measured in advance (it is recommended to be ≥400mm during maintenance).

Installation method:

Hoisting: It is suitable for newly-built clean rooms. The hoisting parts need to be pre-buried in advance.

Installation: Suitable for decoration projects, it is fixed on the ceiling keel through brackets. It is necessary to confirm the load-bearing capacity of the keel (the weight of a single FFU is approximately 80-120kg).

2.2 Materials and Sealing Performance

Box material: 304 stainless steel is preferred for clean rooms (anti-corrosion and easy to clean), and 316L stainless steel can be selected for humid environments.

Sealing design: Liquid tank sealing or double rubber strip sealing is adopted between the filter and the box body, with a leakage rate of ≤0.01% (passing the PAO leakage test).