1.The nurse station needs to be located at the main entrance.
2. The internal height of the clean operating room should not be less than 2.7m; The width of the door for surgical carts to enter and exit should not be less than 1.4m, as this is the width of most surgical carts.
3.The area of the medical staff changing area should be based on the applicable number of people, for example, if there are 10 personnel who need to change clothes, it should be at least 10 square meters. The minimum area of the changing room should not be less than 6 square meters.
4. The installation position of the operating table in the real number room should also be considered. The operating table should be located at the center of the cross in the operating room, and the distance between the operating table and the four walls should not be less than 1.8m. The surgical operator's line of sight should be located in the central area of the air supply direction.
5. Every two operating rooms should have a separate hand brushing room, which should not have a door. If a door is to be set up, a foot operated automatic door must also be used. Attention should also be paid to the position of the brush area, as it can affect traffic and hygiene, and should not be set in corridor areas as much as possible.
6. The ceiling of the clean operating room should not have openings. Inspection holes can be opened in the clean area corridor and sealing measures should be taken. Avoid any external air entering the operating room
7. The sockets, switches, various cabinets, viewing lights, etc. installed in the operating room and tool room should be embedded in the wall and not protrude from the wall.
8. Isolation transformers must be installed in the electrical system of the cardiac surgery operating room.
9.At least 3 lighting fixtures at each end of the operating table should have emergency lighting power supply, and at least 1 lighting fixture in a room with therapeutic function should have emergency power supply. Clean operating rooms should be equipped with information interfaces.
10. A surgical work indicator light should be installed on the outside door of the operating room, and a red safety warning sign light should also be installed above the outer door of the radiation resistant operating room, which is interlocked with medical radiation equipment for control.