1. What type of cooling tower is generally selected?
It is generally recommended to choose a low-noise model, especially when installed in a noise-sensitive area. This type of equipment can reduce operating noise while ensuring heat dissipation performance by optimizing the fan blades and shell structure.
2. Why do cooling water use a physical and chemical processor, while chilled water and hot water use a side-flow water processor?
It is recommended to use a physical and chemical processor for open cooling water systems, which effectively controls algae growth and scaling problems through the synergistic effect of physical fields and chemical agents. Closed systems such as chilled water and hot water are more suitable for side-flow processors, which can achieve continuous softening treatment without affecting the operation of the main system.
3. What should be paid attention to when drawing a full heat exchanger system?
The key is to ensure that the heat exchange efficiency is not less than 60%. It is recommended to use a large air volume exhaust design to allow more indoor exhaust air to exchange heat with fresh air. If a rotary heat exchanger is used, remember to reserve a power interface for the motor and communicate with electrical professionals in advance.

4. What is the general wind speed of the supply and return air outlets of the fan coil?
The wind speed of the supply and return air outlets is usually controlled at 1-2m/s. This range can ensure uniform air distribution and avoid excessive blowing or noise. The specific value can be adjusted according to the function of the room. For example, the wind speed can be appropriately reduced in the conference room.
5. For fresh air or exhaust, do you need to add a check valve on each branch pipe when sharing the header?
Yes, all branches must be installed with a check valve. Especially when multiple devices are running in parallel, the check valve can prevent air flow backflow, ensure the stability of the air volume of each branch, and avoid system cross-wind problems.
6. Does the positive-pressure air supply fan placed on the roof also need to be set up in a fan room?
An independent machine room must be set up. The machine room can not only protect the equipment, but also reduce the impact of noise on the surrounding environment through sound insulation design. At the same time, pay attention to the design of the machine room's air intake and exhaust to ensure smooth airflow.
7. Who is on the elevation of the condensate pipe and the air duct?
The air duct is usually arranged below, and the condensate pipe can be parallel or slightly higher than the air duct. When laying out the plane, try to separate the two to avoid crossing. It is recommended to design the condensate system in zones, and the main riser should be as close to the outer wall as possible to facilitate the discharge of condensate to the outdoor diffuser.
8. What is the generally suitable effective ventilation coefficient for single-layer louvers?
The effective ventilation area coefficient of single-layer louvers is generally 0.7, and the coefficient of rainproof louvers is reduced to 0.5 due to the influence of the blade structure. When designing, it is necessary to make corrections according to the actual shielding situation to ensure that the actual ventilation volume of the air outlet meets the design requirements.
9. In general, how thick is the foundation of air-cooled heat pumps, centrifuges, screw machines, and water pumps?
For large equipment such as chillers and heat pumps, the concrete foundation thickness is usually 200mm. Special attention should be paid to the foundation of the water pump. In addition to the concrete base, a shock-absorbing pedestal should be set. The height of the pedestal is determined according to the selected shock absorber model. The specific requirements of the equipment installation drawing should be checked before actual construction.