Clean room cold storage is a special facility that combines the low temperature storage function of cold storage with the clean environment requirements of clean room. It can not only provide a suitable low-temperature environment for the goods, but also strictly control pollutants such as dust particles and microorganisms in the air to ensure that the stored goods are stored under low temperature and clean conditions. The air cleanliness level of the clean room cold storage can reach different grades in the ISO 14644-1 standard, such as ISO level 7 (the number of dust particles greater than or equal to 0.5μm per cubic meter of air does not exceed 352,000) or higher. This is important for storing items that are sensitive to dust, such as precision electronic components, optical lenses, etc.
Structure and layout
1. Shell structure:
Walls and ceilings: Colored steel or stainless steel panels filled with highly efficient insulation materials, such as polyurethane insulation panels. The thickness of this insulation board depends on the temperature requirements of the cold storage, and the low temperature cold storage may require 10-15cm thick insulation board to ensure good insulation performance. At the same time, use a sealant between the board and the board to prevent air leakage and dust from entering.
Grounding: Grounding requires insulation, wear resistance and corrosion resistance. Generally, the insulated floor is first laid, such as polystyrene foam board, and then the concrete layer is poured and the surface is coated with epoxy floor paint to improve the wear resistance and cleanliness of the ground.
2. Air handling system layout:
Supply and return air outlets: The location of the supply air outlet is designed to ensure uniform circulation of air in the warehouse. Generally, the high efficiency air supply outlet (HEPA) can filter out dust particles above 0.3μm, and the filtration efficiency is more than 99.97%. The layout of the return air outlet should consider the effective recovery of air to avoid the formation of air dead corners.
Air conditioning system and purification equipment: equipped with a special air conditioning unit, the unit can not only adjust the temperature and humidity, but also purify the air. At the same time, air filters will also be installed, such as initial effect, medium effect and high efficiency filters, in a certain order to form a multi-level filtration system to effectively remove dust and microorganisms in the air.



3. Layout of internal facilities:
Shelf system: According to the type and quantity of storage items, select the appropriate shelf. For heavier items, such as parts of large medical devices, heavy shelves may be required; For small batches and multi-variety items, such as drug samples, use lightweight shelves or shelves. The material of the shelves is usually stainless steel or sprayed steel, which is easy to clean and disinfect.
Channel design: Reasonable design of the width of the channel to ensure that cargo handling equipment (such as forklifts, trolleys, etc.) can pass smoothly. The channel should generally be maintained with sufficient width, such as the width of the forklift channel may need 2-3 meters, and the width of the car channel can be 1-1.5 meters.
4. Refrigeration equipment selection:
Compressor: Select the compressor according to the volume and temperature requirements of the cold storage. For large clean room cold storage, screw compressor is a more suitable choice, its cooling capacity is large, high efficiency. For example, in a low-temperature clean room cold storage with a volume of 1000 cubic meters, screw compressors can quickly reduce the temperature in the warehouse and maintain a stable temperature of about -18°C.
Evaporators and condensers: Types of evaporators include coolers and row evaporators. The cooling speed of the chiller is fast, which is suitable for occasions with large temperature fluctuations; The tubular evaporator is suitable for cold storage where the temperature is stable. The condenser is usually air-cooled or water-cooled. The air-cooled condenser is easy to install and suitable for small clean room cold storage. Water-cooled condenser has good cooling effect, but it needs a stable cooling water supply, which is suitable for large cold storage.