A semiconductor cleanroom is a critical infrastructure in the semiconductor manufacturing process. Its design, construction, and operation must strictly comply with high-precision technical standards to ensure a contamination-free environment and guarantee the yield and reliability of chip production.
Cleanliness Class
Cleanrooms shall meet the ISO 14644-1 standard, with a typical class of ISO Class 3 or higher. Specific parameters include no more than 1,000 particles of ≥0.1μm per cubic meter (for ISO Class 3).
Critical process areas such as lithography zones require ISO Class 1 or 2, with a particle control target of no more than 10 particles of ≥0.1μm per cubic meter.
Cleanliness monitoring shall be performed in real-time using particle counters, with data recording intervals not exceeding 1 minute.
Temperature and Humidity Control
The ambient temperature shall be maintained within 22°C ±0.5°C, and the relative humidity (RH) within 45% ±5% RH.
Temperature fluctuations shall be less than 0.1°C per hour, and humidity fluctuations less than 3% RH per hour to prevent electrostatic accumulation and material deformation.
The air conditioning system shall adopt precision control units equipped with redundant refrigeration and humidification equipment to ensure year-round stability.


Pressure Control
Cleanrooms shall maintain a positive pressure gradient: generally, the pressure difference between the main clean area and adjacent areas is ≥15 Pa, and between critical process areas and corridors is ≥25 Pa.
Airflow shall flow from cleaner areas to less clean areas to prevent external contamination intrusion.
The pressure monitoring system shall have an automatic alarm function, triggering immediately when deviations exceed ±5 Pa.
Airflow Pattern and Filtration System
Airflow design adopts unidirectional vertical or horizontal laminar flow, with wind speed controlled at 0.45 m/s ±0.1 m/s (for ISO Class 3 and above).
The filtration system must use ULPA filters (efficiency ≥99.999% for particles ≥0.12μm) or HEPA filters (efficiency ≥99.97% for particles ≥0.3μm). In-situ testing is required after filter installation to ensure a leakage rate below 0.01%.
Air change rates are set according to cleanliness classes; for example, ISO Class 3 areas require ≥500 air changes per hour.
Material and Surface Treatment
All internal surfaces (walls, floors, ceilings) shall use smooth, non-porous, antistatic materials such as epoxy resin coatings or stainless steel, with surface resistivity ranging from 10⁶ to 10⁹ Ω/sq.
Joints shall be sealed to avoid particle accumulation.
Equipment and furniture design must be compatible with cleanrooms, free of shedding and corrosion.
Personnel and Material Management
Personnel shall enter and exit through airlock chambers, wearing full cleanroom suits (including hoods, gloves, and boot covers) that meet the IEST-RP-CC003.3 standard for particle emission testing.
Materials shall be transferred via double-layer pass-through boxes or automatic airlock systems, with surface cleaning and particle monitoring conducted before entry.
The changing procedure includes an air shower with wind speed ≥20 m/s and duration ≥15 seconds.
Monitoring and Alarm System
Environmental parameters (particles, temperature, humidity, pressure difference) shall be monitored in real-time through a distributed sensor network, with a data sampling frequency of no less than once per minute.
The system integrates a SCADA or BMS platform, featuring multi-level alarm thresholds (e.g., temperature deviation ±1°C, humidity deviation ±10% RH), and automatic recording and reporting functions.
Sensors require regular calibration, with precision requirements: temperature ±0.1°C, humidity ±2% RH, pressure difference ±1 Pa.
Vibration and Electrostatic Control
The cleanroom structure shall isolate external vibrations, with a floor vibration velocity limit of ≤25 μm/s (frequency range 8-100 Hz).
Electrostatic control is achieved through ionization systems and grounding measures, maintaining surface potential within ±100 V.
The balance voltage deviation of ionization equipment shall not exceed ±10 V.
Lighting and Noise
The lighting system uses cleanroom-specific fixtures, with an illumination level of 500-1000 lux and uniformity ≥0.8. Fixtures shall be sealed and dustproof.
The noise control target is ≤65 dB(A), and ≤55 dB(A) in sensitive areas (e.g., metrology zones) to avoid interference with precision instruments.
Maintenance and Qualification
Establish a regular maintenance plan, including filter replacement (every 12-24 months), surface cleaning (once daily), and system calibration (every 6 months).
Cleanroom performance qualification shall be conducted in accordance with ISO 14644-2, with a comprehensive test performed annually covering particle counting, airflow uniformity, and leakage detection.
All records shall be retained for at least 5 years for audit purposes.
The above key points ensure that semiconductor cleanrooms meet high reliability standards in technical parameters, suitable for critical process stages such as wafer fabrication, packaging, and testing. Implementation shall be combined with specific facility design, incorporating risk assessment and dynamic optimization.